MGE Office Protection systems: Pulsar 1500 & Pulsar 1500RT2U
Characteristics 700 1000 - 1000 RT2U 1500 - 1500 RT2U
Rating 700 VA / 630 W 1000 VA / 900 W(1) 1500 VA / 1350 W(1)
Format Mini tower Mini tower or RT2U (tower/rack 2U)
Electrical characteristics
Architecture On-line double conversion with automatic by-pass and power factor correction
Input voltage and frequency ranges without using batteries 100/120/140/160 V(2) to 284V - 40 to 70 Hz
Output voltage and frequency 120V (adjustable to 100/110/127 V), 50/60 Hz auto-select or frequency converter mode(3)
Connections
Inputs 5-15P
Outputs (4) 5-15R Tower, (6) 5-15R RT2U
Remotely controlled Powershare sockets (2) NEMA 5-15 receptacles
Additional outputs with HotSwap (4) NEMA 5-15R
Additional outputs with FlexPDU (10) NEMA 5-15R, (10) NEMA 5-15/20R, (8) NEMA L5-20R
Batteries (Typical backup times for 50 and 70% of the VA rating)
Pulsar 16 min / 10 min 18 min / 12 min 13 min / 9 min
Pulsar + 1 EXB - 75 mn / 50 mn 50 mn / 35 mn
Pulsar + 4 EXB - 250 mn / 200 mn 180 mn / 120 mn
Battery management Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition of external battery units => continuous maximisation of backup time + deep discharge protection
Interfaces
Indicators and display 3 LEDS + adjustable multilingual display: display of measurements, access to control and set-up menus
Communication ports 1 USB port + 1 RS232 serial port and relay contacts(4) + 1 mini terminal block for remote ON/OFF and emergency stop
Communications card slots 1 slot for NMC Minislot 2006 card (included in Netpack version) or NMC ModBus/JBus or MC Contacts/Serial
Operating conditions, standards and approvals
Operating temperature noise level 0°C to 40°C continuous, 45 dBA
Performance - Safety - EMC IEC 62 040-3 (VFI-SS-113), IEC 62-040-1-1, IEC 60-950-1 (RD), FCC Subpart B, class A
Approvals UL, cUL, CE, CB report
Dimensions (H x W x D) / Weight
Pulsar 9.52 x 6 x 17.32 in. / 27.5 lbs. 9.52 x 6.17.32 in. / 33 lbs. 9.52 x 6 x 19.29 in. / 39.6 lbs.
Pulsar RT2U - 3.4 x 17.24 x 19in. / 39.6 lbs. 3.4 x 17.24 x 19in. / 45 lbs.
Pulsar EXB - 9.52 x 6 x 17.32 in. / 46.3 lbs.
Pulsar EXB RT2U - 3.4 x 17.24 x 19 in. / 54 lbs.

(1): Maximum rating with EXB battery units: Pulsar 1000 = 800 W, Pulsar 1500 =1200 W. (2): Lower limits for <20 %, <33 %, <66 %, >=66 % of nominal power (VA). For active output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively. (3): Derated by 15% when used as a frequency converter. (4): USB and RS232 serial ports cannot be used simultaneously.

Part numbers 700 1000 1500
Pulsar 86700 86701 86703
Pulsar RT2U (includes rack kit) - 86702 86704
Pulsar EXB - 86705
Pulsar EXB RT2U (includes rack kit) - 86706